Vectec - Total Fuel Management

Below Ground Fuel Storage Tanks

 

Envirotank A below ground fuel tank is an inner fuel storage tank, externally encased within an outer weatherproof bund to ensure any leakage or nominal overfill situation is safely contained.

The below ground fuel tank is easily transportable as a one-piece unit
and reduces costly and time consuming site work.

An underground fuel tank is delivered by our transport to the customers premises. 

ADVANTAGES

• Continuous monitoring for total environmental protection.
• Product stocks are safely contained.
• Tank continuously under test throughout it's life
• Tanks can be encased in a suitable granular or concrete back fill.
• Multi compartment tanks available to customers requirements.
• Below ground fuel storage saves site space.
• Design approved by leading oil companies.
• Accurate gauging systems available (pressure and ultrasonic).

 

Ref Capacity ltr O/A length
inner tank
Inside dia
inner tank
O/A length
outer skin
Dia of outer skin Weight kg
E01 2000  1404  1500  1416  1530  900 
E02 5000  3235  1500  3250  1530  1200 
E17 7000  2803  1900  2815  1930  1900 
E03 10,000  3970  1900  3985  1930  2100 
E04 12,000  4725  1900  4740  1930  2600 
E18 13,637  2708  2743  2720  2773  2800 
E05 15,000  5900  1900  5915  1930  3000 
E88 18,184  4153  2500  4165  2530  3375 
E06 20,000  4610  2500  4625  2530  3700 
E08 25,000  4770  2743  4785  2773  4400 
E90 27,275  6045  2500  6054  2530  4670 
E09 30,000  6810  2500  6825  2530  5300 
E22 31,821  5791  2743  5803  2773  5380 
E98 35,000  7678  2500  7690  2530  6050 
E92 36,368  7968  2500  7980  2530  5830 
E11 40,000  8656  2500  8668  2530  6700 
E24 40,913  7315  2743  7327  2773  6750 
E25 45,459  8052  2743  8064  2773  7200 
E13 50,000  10,754  2500  10,766  2530  8150 
E26 54,551  9754  2743  9766  2773  8510 
E97 55,000  11,803  2500  11,815  2530  8650 
E15 60,000  12,853  2500  12,865  2530  9700 
E96 68,189  14,571  2500  14,583  2530  10,410
E99 100,000  MAXIMUM AVAILABLE VOLUME ON REQUEST

Note that the dimensions listed above may vary depending on the site and tank capacity requirements. Other tank capacities can be designed on request.

 

Additional Fittings

• Holding down straps with ratchet straps.
• Tank contents gauges.
• Dipsticks.
• Overfill prevention valve with or without offset fill adapters.
• Internal fill pipes.
• Internal suction pipes.
• Leak detection devices (dry pressure or vacuum) available complete with remote alarm unit, relay and probe.
• Installation kit for leak detection device.
• Manway flanges for connecting GRP access chambers.

 

 